The significance of industrial switch ring network configuration is to improve network reliability, enhance fault tolerance and self-healing capabilities, optimize performance and facilitate expansion management, ensuring stable and efficient operation of the network in an industrial environment.
Hirschmann ringring network configuration has two ways:

One is to set the ring network by the switch DIP switch. The DIP switch is used to enable functions and RM roles separately. The physical DIP has strict requirements on the port. After the DIP is pulled, the ring network switch can only be interconnected through Port1.1 and Port1.2 and cannot be modified.
Another soft configuration, aka web interface configuration, is more flexible and more convenient to observe parameters. This article mainly explains web interface configuration, and the following are related cases.
Note: First disconnect the switch ring network and make the network into a bus structure to avoid physical rings causing network storms. Set all the DIP switches of the switch to ON (DIP on the right). Only in this way will the switch software configuration not conflict with the DIP switch function.

Step 1: Select the physical port as the Hiper-ring port. You can choose an electrical port or an optical port to ensure that the ports at both ends automatically negotiate and have the same speed.
Select the backbone high-speed optical port

Step 2: Disable the spanning tree protocol on the ring network port
Method 1: Enter as shown in the figure below. If you specify ports 6.1 and 6.2 as ring ports, uncheck the "STP State Enable" option to turn off the STP function;
Shut down a single interface

Method 2: Enter as shown in the figure below, select "off" in the "Operation" radio button to turn off the RSTP function of the entire switch; this method is risky (Note, if there is no special situation, such as method 1 cannot turn off the STP function of a single port, then choose to turn it off globally)

Step 3: Configure Hiper-ring function
Version: Select the ring network protocol version. Here, select HIPER-Ring.
HIPER-Ring: Hirshcmann private ring
MRP: Male standard ring

Port1 and Ring Port2: Select or enter the port number to be set as the ring port.
Module: The module where the ring network port is located (the integrated module is 1, and the modular module is calculated according to the slot, from left to right, starting from 1)
Port: Ring network port
Operation: Display the ring network port status
Active: Indicates that the ring network port is activated, the port is open or online
Inactive: Indicates that the ring network port is not online or disabled

Ring Manager Status: Redundancy status (displayed only on the redundancy manager, non-RM does not display status information)
Active: Indicates that the ring network redundant line is activated, and a line or device in the ring network fails [fault-enabled ring mechanism]
Inactive: Indicates that the ring network is working normally, no faults have occurred, and the redundant line is in standby state [normal state]

Ring Manager: Set RM. A ring network can only have one ring manager, which is used to send and receive ring network detection information frames.
On: Select this option to use the currently configured switch as the ring redundancy manager
Off: Select this option to use the currently configured switch as a general switch in the ring network.