Weidmuller WDU 70/95 1024600000
Feed-through terminal block, Screw connection, dark beige, 95 mm², 232 A, 1000 V, Number of connections: 2
General ordering data
|
Version |
Feed-through terminal block, Screw connection, dark beige, 95 mm², 232 A, 1000 V, Number of connections: 2 |
|
Order No. |
1024600000 |
|
Type |
WDU 70/95 |
|
GTIN (EAN) |
4008190105990 |
|
Qty. |
10 items |
Dimensions and weights
|
Depth |
107 mm |
|
Depth (inches) |
4.213 inch |
|
Depth including DIN rail |
115.5 mm |
|
Height |
132 mm |
|
Height (inches) |
5.197 inch |
|
Width |
27 mm |
|
Width (inches) |
1.063 inch |
|
Net weight |
330.89 g |
Temperatures
|
Storage temperature |
-25 °C...55 °C |
|
Operating temperature range |
For operating temperature range see EC Design Test Certificate / IEC Ex-Certificate of Conformity |
|
Continuous operating temp., min. |
-60 °C |
|
Continuous operating temp., max. |
130 °C |
Environmental Product Compliance
|
RoHS Compliance Status |
Compliant without exemption |
|
REACH SVHC |
No SVHC above 0.1 wt% |
Material data
|
Material |
Wemid |
|
Colour |
dark beige |
|
UL 94 flammability rating |
V-0 |
Rating data IECEx/ATEX
|
Certificate No. (ATEX) |
DEMKO14ATEX1338U |
|
Certificate No. (IECEX) |
IECEXULD14.0005U |
|
Max. voltage (ATEX) |
1100 V |
|
Current (ATEX) |
218 A |
|
Wire cross section max. (ATEX) |
95 mm² |
|
Max. voltage (IECEX) |
1100 V |
|
Current (IECEX) |
218 A |
|
Wire cross section max. (IECEX) |
95 mm² |
|
Operating temperature range |
For operating temperature range see EC Design Test Certificate / IEC Ex-Certificate of Conformity |
|
Marking EN 60079-7 |
Ex eb II C Gb |
|
Ex 2014/34/EU label |
II 2 G D |
System specifications
|
Version |
Screw connection |
|
End cover plate required |
No |
|
Number of potentials |
1 |
|
Number of levels |
1 |
|
Number of clamping points per level |
2 |
|
Number of potentials per tier |
1 |
|
Levels cross-connected internally |
No |
|
PE connection |
No |
|
Rail |
TS 35 |
|
N-function |
No |
|
PE function |
No |
|
PEN function |
No |
2 clampable conductors (H05V/H07V) with equal cross-section (rated connection)
|
Cross-section for connected wire, stranded, two clampable wires, max. |
35 mm² |
|
Cross-section for connected wire, stranded, two clampable wires, min. |
16 mm² |
|
Wire connection cross section, finely stranded with wire-end ferrules DIN 46228/1, 2 clampable wires, max. |
35 mm² |
|
Wire connection cross section, finely stranded with wire-end ferrules DIN 46228/1, 2 clampable wires, min. |
16 mm² |
|
Wire connection cross section, finely stranded, two clampable wires, min. |
16 mm² |
|
Wire cross-section, finely stranded, two clampable wires, max. |
35 mm² |
Additional technical data
|
Explosion-tested version |
Yes |
|
Installation advice |
Direct mounting |
|
Number of similar terminals |
1 |
|
Open sides |
closed |
|
Type of mounting |
Snap-on |
Conductors for clamping (additional connection)
|
Connection type, additional connection |
Screw connection |
Conductors for clamping (rated connection)
|
Blade size |
S6 (DIN 6911) |
|
Clamping range, max. |
120 mm² |
|
Clamping range, min. |
13.3 mm² |
|
Clamping screw |
M 8 |
|
Connection cross-section, stranded, max. |
120 mm² |
|
Connection cross-section, stranded, min. |
16 mm² |
|
Connection direction |
on side |
|
Gauge to IEC 60947-1 |
B12 |
|
Number of connections |
2 |
|
Stripping length |
30 mm |
|
Tightening torque, max. |
12 Nm |
|
Tightening torque, min. |
6 Nm |
|
Type of connection |
Screw connection |
|
Wire connection cross section AWG, max. |
AWG 2/0 |
|
Wire connection cross section AWG, min. |
AWG 6 |
|
Wire connection cross section, finely stranded, max. |
95 mm² |
|
Wire connection cross section, finely stranded, min. |
16 mm² |
|
Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/1, max. |
95 mm² |
|
Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/1, min. |
16 mm² |
|
Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/4, max. |
50 mm² |
|
Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/4, min. |
16 mm² |
|
Wire connection cross-section, solid core, max. |
16 mm² |
|
Wire connection cross-section, solid core, min. |
16 mm² |
CSA rating data
|
Certificate No. (CSA) |
12400-242 |
|
Current size B (CSA) |
205 A |
|
Current size C (CSA) |
205 A |
|
Current size D (CSA) |
5 A |
|
Voltage size B (CSA) |
600 V |
|
Voltage size C (CSA) |
600 V |
|
Voltage size D (CSA) |
600 V |
|
Wire cross section max. (CSA) |
00 AWG |
|
Wire cross section min. (CSA) |
6 AWG |
General
|
Installation advice |
Direct mounting |
|
Rail |
TS 35 |
|
Standards |
IEC 60947-7-1 |
|
Wire connection cross section AWG, max. |
AWG 2/0 |
|
Wire connection cross section AWG, min. |
AWG 6 |
Rating data
|
Rated cross-section |
95 mm² |
|
Rated voltage |
1,000 V |
|
Rated DC voltage |
1,000 V |
|
Rated current |
232 A |
|
Current at maximum wires |
232 A |
|
Standards |
IEC 60947-7-1 |
|
Volume resistance according to IEC 60947-7-x |
0.14 mΩ |
|
Rated impulse withstand voltage |
8 kV |
|
Power loss in accordance with IEC 60947-7-x |
7.42 W |
|
Pollution severity |
3 |
UL rating data
|
Certificate No. (UR) |
E60693 |
|
Conductor size Factory wiring max. (UR) |
00 AWG |
|
Conductor size Factory wiring min. (UR) |
6 AWG |
|
Conductor size Field wiring max. (UR) |
00 AWG |
|
Conductor size Field wiring min. (UR) |
6 AWG |
|
Current size C (UR) |
175 A |
|
Voltage size C (UR) |
1000 V |