Phoenix Contact TRIO-PS/3AC/24DC/20 Power Supply Unit 2866394
Product description
The Phoenix Contact TRIO-PS/3AC/24DC/20 primary-switched TRIO POWER power supply for DIN rail mounting, input: Three-phase output. 24 V DC/20 A
The TRIO POWER range of power supplies offers standard functionality for use in machine production. The 1- and 3-phase versions, with a power rating of up to 960 W, are suitable for use worldwide thanks to the wide-range input and international approval package.
Customers are given a dependable and sturdy product because of the sturdy metal housing, strong electric strength, and broad temperature range, which guarantee a high degree of power supply reliability.
Product features
The third negative terminal block can be used as a grounding terminal block, which helps to minimise installation costs. The product features a robust design with a metal housing and a wide temperature range from -25 to +70°C, making it suitable for use in a variety of environments. The product offers maximum operational reliability thanks to a high MTBF (mean time between failures) of more than 500,000 hours and a high dielectric strength of up to 300 V AC. Furthermore, the output voltage can be adjusted at the front to compensate for voltage drops.
Technical data
Input data
AC operation
|
Nominal input voltage range |
3x 400 V AC ... 500 V AC |
|
Input voltage range |
3x 320 V AC ... 575 V AC (Derating < 360 V AC: 1,5 %/V) |
|
2x 360 V AC ... 575 V AC (for 2-phase operation) |
|
|
Extended input voltage range in operation |
3x 320 V AC ... 575 V AC (Derating < 360 V AC: 1,5 %/V) |
|
Input voltage range AC |
3x 320 V AC ... 575 V AC (Derating < 360 V AC: 1,5 %/V) |
|
2x 360 V AC ... 575 V AC (for 2-phase operation) |
|
|
Voltage type of supply voltage |
AC |
|
Inrush current |
< 15 A |
|
Inrush current integral (I2t) |
0.5 A2s |
|
AC frequency range |
45 Hz ... 65 Hz |
|
Mains buffering time |
> 17 ms (3x 400 V AC) |
|
Current consumption |
3x 1.1 A (400 V AC) |
|
3x 0.8 A (480 V AC) |
|
|
Nominal power consumption |
793 VA |
|
Protective circuit |
Transient surge protection; Varistor |
|
Power factor (cos phi) |
0.67 |
|
Typical response time |
< 1 s |
|
Permissible backup fuse |
B6 B10 B16 |
|
Recommended breaker for input protection |
6 A ... 16 A (Characteristics B, C, D, K) |
|
Discharge current to PE |
< 3.5 mA |
Output data
|
Efficiency |
91 % (at 400 V AC and nominal values) |
|
Output characteristic |
U/I |
|
Nominal output voltage |
24 V DC ±1 % |
|
Setting range of the output voltage (USet) |
22.5 V DC 29.5 V DC (> 24 V DC, constant capacity restricted) |
|
Nominal output current (IN) |
20 A (UOUT = 24 V DC) |
|
Derating |
55 °C ... 70 °C (2.5 %/K) |
|
Feedback voltage resistance |
35 V DC |
|
Protection against overvoltage at the output (OVP) |
< 35 V DC |
|
Max. capacitive load |
unlimited |
|
Active current limitation |
Approx. 25 A |
|
Control deviation |
< 1 % (change in load, static 10 % ... 90 %) |
|
< 2 % (change in load, dynamic 10 % ... 90 %) |
|
|
< 0.1 % (change in input voltage ±10 %) |
|
|
Residual ripple |
< 10 mVPP |
|
Output power |
480 W |
|
Peak switching voltages nominal load |
< 30 mVPP |
|
Maximum no-load power dissipation |
< 6 W |
|
Power loss nominal load max. |
< 48 W |
|
Rise time |
< 2 ms (UOUT (10 % ... 90 %)) |
|
Connection in parallel |
yes, for redundancy and increased capacity |
|
Connection in series |
yes |
Connection data
Input
|
Connection method |
Screw connection |
|
Conductor cross section, rigid min. |
0.2 mm² |
|
Conductor cross section, rigid max. |
2.5 mm² |
|
Conductor cross section flexible min. |
0.2 mm² |
|
Conductor cross section flexible max. |
2.5 mm² |
|
Conductor cross section AWG min. |
24 |
|
Conductor cross section AWG max. |
14 |
|
Stripping length |
9 mm |
|
Screw thread |
M2,5 |
|
Tightening torque, min |
0.4 Nm |
|
Tightening torque max |
0.5 Nm |
Output
|
Connection method |
Screw connection |
|
Conductor cross section, rigid min. |
0.5 mm² |
|
Conductor cross section, rigid max. |
6 mm² |
|
Conductor cross section flexible min. |
0.5 mm² |
|
Conductor cross section flexible max. |
4 mm² |
|
Conductor cross section AWG min. |
12 |
|
Conductor cross section AWG max. |
10 |
|
Stripping length |
14 mm |
|
Screw thread |
M3 |
|
Tightening torque, min |
0.5 Nm |
|
Tightening torque max |
0.6 Nm |
Signaling
|
Types of signaling |
LED |
|
Operating voltage display |
Green LED |
Signal output
|
Status display |
"DC OK" LED green |
|
Note on status display |
UOUT > 21.5 V: LED lights up |
Electrical properties
|
Insulation voltage input/output |
4 kV AC (type test) |
|
2 kV AC (routine test) |
|
|
Insulation voltage output / PE |
500 V DC (routine test) |
|
Insulation voltage input / PE |
2 kV AC (type test) |
Product properties
|
Product type |
Power supply |
|
Product family |
TRIO POWER |
|
MTBF (IEC 61709, SN 29500) |
> 1190000 h |
Data management status
|
Article revision |
04 |
Insulation characteristics
|
Protection class |
I (with PE connection) |
|
Overvoltage category |
III |
|
Degree of pollution |
2 |
Dimensions
|
Dimensional drawing |
|
|
Width |
115 mm |
|
Height |
130 mm |
|
Depth |
152.5 mm |
Installation dimensions
|
Installation distance right/left |
0 mm / 0 mm |
|
Installation distance top/bottom |
50 mm / 50 mm |
Mounting
|
Assembly note |
alignable: horizontally 0 mm, vertically 50 mm |
|
Mounting position |
horizontal DIN rail NS 35, EN 60715 |
|
With protective coating |
no |
Material specifications
|
Housing material |
Metal |
|
Type of housing |
Steel sheet, zinc-plated |
|
Side element version |
Aluminum |
Environmental and real-life conditions
Ambient conditions
|
Degree of protection |
IP20 |
|
Ambient temperature (operation) |
-25 °C ... 70 °C (> 55° C derating : 2.5%/K) |
|
Ambient temperature (storage/transport) |
-40 °C ... 85 °C |
|
Climatic class |
3K3 (in acc. with EN 60721) |
|
Max. permissible relative humidity (operation) |
≤ 95 % (at 25 °C, non-condensing) |
|
Shock |
18 ms, 30g, in each space direction (according to IEC 60068-2- 27) |
|
Vibration (operation) |
< 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) |
|
15 Hz ... 150 Hz, 2.3g, 90 min. |
Standards and regulations
|
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations |
EN 50178/VDE 0160 (PELV) |
|
Standard – Limitation of mains harmonic currents |
EN 61000-3-2 |
|
Standard - Electrical safety |
EN 60950-1/VDE 0805 (SELV) |
|
Standard – Protection against shock currents, basic requirements for protective separation in electrical equipment |
EN 50178 |
|
Standard – Safety extra-low voltage |
EN 60950-1 (SELV) |
|
EN 60204 (PELV) |
|
|
Standard - Safe isolation |
DIN VDE 0100-410 |
Approvals
|
UL approvals |
UL/C-UL listed UL 508 |
|
UL/C-UL Recognized UL 60950-1 |
Conformity/Approvals
|
SIL in accordance with IEC 61508 |
0 |
EMC data
|
Electromagnetic compatibility |
Conformance with EMC Directive 2014/30/EU |
|
Low Voltage Directive |
Conformance with Low Voltage Directive 2014/35/EC |
|
EMC requirements for noise emission |
EN 61000-6-3 |
|
EN 61000-6-4 |
|
|
EMC requirements for noise immunity |
EN 61000-6-1 |
|
EN 61000-6-2 |
Electrostatic discharge
|
Standards/regulations |
EN 61000-4-2 |
Electrostatic discharge
|
Contact discharge |
8 kV (Test Level 4) |
|
Discharge in air |
8 kV (Test Level 3) |
|
Comments |
Criterion A |
Electromagnetic HF field
|
Standards/regulations |
EN 61000-4-3 |
Electromagnetic HF field
|
Frequency range |
80 MHz ... 1 GHz |
|
Test field strength |
10 V/m |
|
Frequency range |
1 GHz ... 2 GHz |
|
Test field strength |
10 V/m |
|
Frequency range |
2 GHz ... 3 GHz |
|
Test field strength |
10 V/m |
|
Comments |
Criterion A |
Fast transients (burst)
|
Standards/regulations |
EN 61000-4-4 |
Fast transients (burst)
|
Input |
4 kV (Test Level 4 - asymmetrical) |
|
Output |
4 kV (Test Level 4 - asymmetrical) |
|
Signal |
2 kV (Test Level 3 - asymmetrical) |
|
Comments |
Criterion A |
Surge voltage load (surge)
|
Standards/regulations |
EN 61000-4-5 |
Surge voltage load (surge)
|
Input |
1 kV (Test Level 2 - symmetrical) |
|
2 kV (Test Level 3 - asymmetrical) |
|
|
Output |
0.5 kV (Test Level 1 - symmetrical) |
|
0.5 kV (Test Level 1 - asymmetrical) |
|
|
Comments |
Criterion B |
Conducted interference
|
Standards/regulations |
EN 61000-4-6 |
Conducted interference
|
Frequency range |
0.15 MHz ... 80 MHz |
|
Comments |
Criterion A |
|
Voltage |
10 V (Test Level 3) |
Voltage dips
|
Standards/regulations |
EN 61000-4-11 |
Emitted interference
|
Standards/regulations |
EN 61000-6-3 |
|
Radio interference voltage in acc. with EN 55011 |
EN 55011 (EN 55022) Class B, area of application: Industry and residential |
|
Emitted radio interference in acc. with EN 55011 |
EN 55011 (EN 55022) Class B, area of application: Industry and residential |


Hot Tags: phoenix contact trio-ps/3ac/24dc/20 2866394, China, wholesale, online, order, Phoenix Contact ST 2 5 3031212, phoenix contact crimpfox, Phoenix Contact WIREFOX 2 5 1212368, Phoenix Contact FL SWITCH SFNB 5TX 2891001, Phoenix Contact TRIO PS 2G1AC24DC10 2903149, Phoenix Contact CRIMPFOX CENTRUS 6S 1213144